Do's :
- Keep the VRLA batteries away from heat, sparks, fire etc.
- Clean the VRLA batteries as and when dust accumulates.
- Charge the VRLA batteries once in every six months @ 13.8V VPC for 24 hrs. If stored for longer periods
- Wherever cables are used ensure using proper cable size and crimping of the plug to the cable
- Torque all terminal bolts to 11 Nm (100 Lb.-inch)
- Re- torque the terminal bolts once in every six months
- After discharge, recharge the batteries when power restores
- Always use calibrated instruments for measurements
Dont' s :
- Do not tamper with the safety valves
- Do not over-tighten the terminal bolts
- Do not allow any metal objects to fall across the battery terminals
- Do not mix VRLA batteries of different capacities or makes
- Do not mix ordinary conventional/low maintenance VRLA batteries with Amaron Quanta SMF Batteries
- Do not install physically damaged batteries
- Do not make any tap connections from the VRLA battery bank
- Do not boost charge the VRLA batteries for more than 12 Hrs. in regular operation / usage
- Do not allow any direct sunlight to fall on batteries