Main menu:
Constant voltage current limiting charging method is most suitable for Amaron Quanta -
Float Mode : 13.50Volts
Boost Mode : 13.80Volts
Current Limit : 25% of rated Ah
Ripple allowable : < 2% rms
O/P Voltage regulation : ±1%
Over Voltage cut off : 14.00Volts
Under Voltage Trip : 10.50Volts